The IS-mC1 is a compact
combined 100dB(A) alarm sounder and L.E.D. beacon - only one Zener
barrier or galvanic isolator required to run both sounder & beacon
or alternatively the unit can be operated as individual signals.
Approvals include ATEX, IECEx and GOST-R for Zone 0 applications and FM approval for Class I Division 1
and Class I Zone 0 applications.
Specification
|
Alarm sounder: |
Nominal output: |
100dB(A) @ 1m +/- 3dB - Tone 2* [91dB(A) @ 10ft/3m] |
No. of tones: |
49 (UKOOA/PFEER compliant) |
No. of stages: |
3 |
Volume control: |
Max. 100dB(A); Min. 90dB(A) - Tone 2 |
Effective range: |
40m/131ft @ 1KHz |
L.E.D. Beacon: |
|
Light source: |
Array of 6 high intensity L.E.D’s. |
L.E.D. colours: |
Red, Amber, Blue, Green & Clear |
Flash modes: |
Double flash at 2Hz and 1Hz |
Effective intensity cd: |
23cd* - measured ref. to I.E.S. |
General: |
Voltage: |
16-28vdc via Zener barrier or galvanic isolator |
Combined current: |
approx: 30mA typical when powered from 24v supply via 28v 300Ohm Zener barrier. |
Ingress protection: |
IP65 |
Rating: |
Continuous |
Housing material: |
UL94V0 & 5VA FR ABS & PC |
Housing colour: |
RAL3000 Red |
Fixings: |
Stainless Steel |
Cable entries: |
2 x M20 clearance gland knockouts. Custom configurations also available. |
Terminals: |
0.5 to 2.5mm² |
Operating temp: |
-40° to +60°C [-40° to +140°F] |
Storage temp: |
-40° to +70°C [-40° to +158°F] |
Relative humidity: |
90% at 20°C [68°F] |
Combined or Sounder only: May be powered from any certified Zener barrier or galvanic isolator whose output parameters do not exceed : |
Uo: 28vdc | Io: 93mA | Po: 660mW |
|
Beacon only: May be powered from any certified Zener barrier or galvanic isolator whose output parameters do not exceed : |
Uo: 28vdc | Io: 660mA | Po: 1.2W |
ATEX / IECEx / FM |
II 1G Ex ia IIC T4 Ga (-40ºC <=Ta<= +60°C) |
IS Class l, Division 1, Groups A, B, C, D T4 |
IS Class I, Zone 0, AEx ia IIC T4 Ta = +60°C |
|
GOST-R |
0ExiaIICT4 IP65 -40° to +60°C |